| MAINS POWER SUPPLY RATING |
90V AC a 230V AC |
| PRIMARY DC SUPPLY |
28.5V DC @ 2.4 A (Max) |
| SECONDARY SUPPLY |
21.6 (Min) – 27.2V DC (Max) – Battery charger: 27.5V DC |
| BATTERY MAXIMUM CAPACITY (INTERNA) |
Standard box: 2x 12V 7AH; Deep box: 2x 12V 12AH |
| QUIESCENT CURRENT (NO DEVICES) |
52 mA |
| AUX POWER OUTPUT |
2 x 24V DC 300mA / 1 x 24V switched output |
| MAXIMUM LOOP OUTPUT CURRENT |
1 loop – 900mA alarm peak / 165mA quiescent |
| LOOP TOPOLOGY |
Class A (loop) or Class B (radial) |
| LOOP CABLE |
Fire resistant 2 x 1.5mm (max 1200m) or 2 x 2.5mm (max 2000m) |
| CONVENTIONAL SOUNDER CIRCUITS |
500mA for conventional sounder circuits a+b |
| AUX. RELAYS FIRE |
2 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive |
| AUX. RELAY FAULT |
1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive |
| GRAPHICAL LCD DISPLAY |
High definition, high contrast blue backlit 240×64 pixels |
| COMMUNICATION CHANNELS |
2 x configurable communication ports |
| BMS OUTPUTS |
ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4 |
| SOFTWARE CONNECTION |
USB type B |
| EVENT LOG |
10000 events |
| OPERATING/ STORAGE TEMPERATURE |
-10ºC to +55ºC |
| HUMIDITY |
Max. 85% RH Non-Condensing |
| INGRESS PROTECTION / MATERIAL |
IP30 / ABS |
| DIMENSIONS |
Standard box: 273 (L) x 404 (H) x 107 (W) mm Deep box: 273 (L) x 404 (H) x 142 (W) mm |
| WEIGHT |
1.6 Kg (no batteries) |
| COLOUR |
White (RAL 9003), Red (RAL 3001) or Anthracite (RAL 7016) |