Key Features:
- Expandable from 1 to 4 loops
- Network compatibility with the G-One, GEKKO and NODE+ control panels
- Connection to the repeater panels via RS422, Fibre-Optic or TCP/IP
- 250 devices per loop (125 address limit)
- Up to 95 VULCAN 2 (addressable) ultra low current base sounders (32 address limit)
- 32 individually programmable sounder addresses
- Full Self-Addressing Device support
- 2 Fire output relays (change-over) and 1 Fault relay (NC )
- 2 conventional alarm outputs (individually programmable)
- Loops fully monitored for high integrity
- 384 fully programmable zones
- 512 fully programmable sounder groups; 512 I/O groups
- Event log (10000 events)
- Available with ZEOS digital protocol
- Compatible with all ancillary modules
- Backlit graphical LCD display of 240×64 pixels
- Programming by integrated tactile keypad or Loader PC software
- Multiple language support (menu selectable)
- Integrated 16 LED fire zone indications
- Installer friendly Auto-learn facility
- Certified to EN54 parts 2 and 4
- Approval in EN54 part 13
Technical Specification:
- MAINS POWER SUPPLY RATING:- 90V a 253V @ 50 Hz 65 W
- PRIMARY DC SUPPLY:- 28.5V DC @ 2.4 A (Max)
- SECONDARY SUPPLY:- 21.6V DC (Min.) – 27.2V DC (Max) – Battery charger: 27.5V DC
- PRIMARY ADDRESSABLE DETECTION AND ALARM CIRCUIT:- 28.5V DC
- SOUNDERS CONVENTIONAL OUTPUT CIRCUIT:- 28V DC
- BATTERY MAXIMUM CAPACITY (INTERNAL):- 2x 12V 12AH
- QUIESCENT CURRENT (NO DEVICES):- 64 mA
- AUX POWER OUTPUT:- 2x 24V DC 300mA / up to 1 x 24V switched output
- MAXIMUM LOOP OUTPUT CURRENT:- 1-4 loop – Max. 165 mA per loop quiescent / Max. 900mA per loop peak
- LOOP TOPOLOGY:- Class A or Class B
- LOOP/SOUNDER CABLE:- Firetuf 2 x 1.5mm (Max. 1200m) or 2 x 2.5mm (Max. 2000m)
- CONVENTIONAL SOUNDER CIRCUITS:- 500mA for conventional sounder circuits a+b
- AUX. RELAYS FIRE:- 2x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
- AUX. RELAY FAULT:- 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
- GRAPHICAL LCD DISPLAY:- High definition, high contrast blue backlit 240×64 pixels
- COMMUNICATION CHANNELS:- 3x configurable communication ports
- BMS OUTPUTS:- ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
- SOFTWARE CONNECTION:- USB type B
- EVENT LOG:- 10000 events
- OPERATING/ STORAGE TEMPERATURE:- -10ºC to +50ºC
- HUMIDITY:- Max. 85% RH Non-Condensing
- INGRESS PROTECTION / MATERIAL:- IP30 / ABS
- DIMENSIONS:- 345 (L) x 375 (H) x 139 (W) mm
- WEIGHT:- 7.5 Kg – 10,5 Kg (inc. battery)