Node+ Expansion For Octo+ Systems 1 – 4 Loop Fire Alarm Control Panel:

Key Features:

  • Expandable from 1 to 4 loops
  • Network compatibility with the G-One, GEKKO and NODE+ control panels
  • Connection to the repeater panels via RS422, Fibre-Optic or TCP/IP
  • 250 devices per loop (125 address limit)
  • Up to 95 VULCAN 2 (addressable) ultra low current base sounders (32 address limit)
  • 32 individually programmable sounder addresses
  • Full Self-Addressing Device support
  • 2 Fire output relays (change-over) and 1 Fault relay (NC )
  • 2 conventional alarm outputs (individually programmable)
  • Loops fully monitored for high integrity
  • 384 fully programmable zones
  • 512 fully programmable sounder groups; 512 I/O groups
  • Event log (10000 events)
  • Available with ZEOS digital protocol
  • Compatible with all ancillary modules
  • Backlit graphical LCD display of 240×64 pixels
  • Programming by integrated tactile keypad or Loader PC software
  • Multiple language support (menu selectable)
  • Integrated 16 LED fire zone indications
  • Installer friendly Auto-learn facility
  • Certified to EN54 parts 2 and 4
  • Approval in EN54 part 13

Technical Specification:

  • MAINS POWER SUPPLY RATING:- 90V a 253V @ 50 Hz 65 W
  • PRIMARY DC SUPPLY:- 28.5V DC @ 2.4 A (Max)
  • SECONDARY SUPPLY:- 21.6V DC (Min.) – 27.2V DC (Max) – Battery charger: 27.5V DC
  • PRIMARY ADDRESSABLE DETECTION AND ALARM CIRCUIT:- 28.5V DC
  • SOUNDERS CONVENTIONAL OUTPUT CIRCUIT:- 28V DC
  • BATTERY MAXIMUM CAPACITY (INTERNAL):- 2x 12V 12AH
  • QUIESCENT CURRENT (NO DEVICES):- 64 mA
  • AUX POWER OUTPUT:- 2x 24V DC 300mA / up to 1 x 24V switched output
  • MAXIMUM LOOP OUTPUT CURRENT:- 1-4 loop – Max. 165 mA per loop quiescent / Max. 900mA per loop peak
  • LOOP TOPOLOGY:- Class A or Class B
  • LOOP/SOUNDER CABLE:- Firetuf 2 x 1.5mm (Max. 1200m) or 2 x 2.5mm (Max. 2000m)
  • CONVENTIONAL SOUNDER CIRCUITS:- 500mA for conventional sounder circuits a+b
  • AUX. RELAYS FIRE:- 2x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
  • AUX. RELAY FAULT:- 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
  • GRAPHICAL LCD DISPLAY:- High definition, high contrast blue backlit 240×64 pixels
  • COMMUNICATION CHANNELS:- 3x configurable communication ports
  • BMS OUTPUTS:- ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
  • SOFTWARE CONNECTION:- USB type B
  • EVENT LOG:- 10000 events
  • OPERATING/ STORAGE TEMPERATURE:- -10ºC to +50ºC
  • HUMIDITY:- Max. 85% RH Non-Condensing
  • INGRESS PROTECTION / MATERIAL:- IP30 / ABS
  • DIMENSIONS:- 345 (L) x 375 (H) x 139 (W) mm
  • WEIGHT:- 7.5 Kg – 10,5 Kg (inc. battery)
  • COLOUR:- White (RAL 9003), Red (RAL 3001) or Anthracite (RAL 7016)
Category: Tag: