QUAD-ZMU Addressable Monitoring Unit of multiple Conventional Zones:

The QUAD-ZMU is a fully monitored addressable module which is used to connect up to four individually addressed zones of current-limited conventional detection devices to GFE’s addressable control panel via the detection loop.

The module requires an external 24V DC power supply and a green LED indicates supply presence. QUAD ZMU provides active end of line monitoring. The module is compliant with Standard BS5839 Detector Removal when Schottky diodes are added to detector bases.

The detection zones and their supply voltage are optically isolated from the addressable detection loop which enables the use of a local power supply. If that supply fails, a fault condition is reported at the control panel.

The status of each zone is indicated by two LEDs. A red LED signals fire, a yellow LED indicates a fault on that zone. The normal state is indicated by neither LEDs being illuminated.

Technical Specification:

  • SUPPLY VOLTAGE / LOOP CURRENT:- 20V to 30V DC / 1.6 mA
  • EXT. SUPPLY CURRENT @ 24V DC:- 5.3 mA Quiescent – per zone OC/ SC/ FIRE – 7 / 33 / 23 mA
  • MAX. CABLE SIZE:- 2.5 mm²
  • COLOUR / CASE MATERIAL:- White & Transparent / ABS & PC
  • OPER. TEMPERATURE:- -10ºC to 50ºC
  • MAX. HUMIDITY:- 95% RH Non-Condensing
  • DIMENSIONS:- 150 (W) x 90 (L) x 32 (H) mm
  • WEIGHT:- 220 g – boxed
Category: Tag: