Key Features:
- 1 to 4 loops panel
- Supports connection to Repeaters via RS422, Fibre-Optic or TCP/IP
- Networkable panel, compatible with OCTO+ and NODE+ range of panels
- Up to 250 devices per loop (only 125 addresses available)
- Up to 95 VULCAN 2 (addressable) ultra low current base sounders (32 address limit)
- 32 individually programmable sounder addresses
- Full Self-Addressable Devices support
- 2 Fire output relays (change-over) and 1 Fault relay (NC – opens on fault)
- 2 conventional alarm outputs (Individually programmable)
- Both detection loops monitored for integrity
- 512 fully programmable sounder and I/O groups
- 384 fully programmable zones
- Event log (rolling, 10000 entries)
- Available only with ZEOS protocol
- Compatible with all our own low cost ancillary modules
- Backlit graphical LCD display of 240×64 pixels
- Programming by integrated keypad or Loader PC software
- Multiple language support (menu selectable)
- Integrated 16 zone LED fire zone indication.
Key Features:
- MAINS POWER SUPPLY RATING:- 90V to 253V @ 50Hz 65W
- PRIMARY DC SUPPLY:- 28.5V DC @ 2.4A (Max)
- SECONDARY SUPPLY:- 21.6 (Min) – 27.2V DC (Max) – Battery charger: 27.5V DC
- PRIMARY ADDRESSABLE DETECTION AND ALARM CIRCUIT:- 5V DC
- SOUNDERS CONVENTIONAL OUTPUT CIRCUIT:- 28V DC
- BATTERY CAPACITY (INTERNAL) :- Standard box: 2x 12V 7AH; Deep Box: for larger volume batteries
- QUIESCENT CURRENT (NO DEVICES) :- 60mA
- AUX POWER OUTPUT:- 2 x 24V DC 300mA / 1 x 24V switched out
- MAXIMUM LOOP OUTPUT CURRENT:- 1 – 4 loops 900mA alarm peak / 165mA quiescent per loop
- LOOP TOPOLOGY:- Class A (loop) or Class B (radial)
- LOOP/SOUNDER CABLE:- Fire resistant 2 x 1.5mm (Max 1200 m) or 2 x 2.5mm (Max 2000 m)
- CONVENTIONAL SOUNDER CIRCUITS:- 500mA for conventional sounder circuits a+b
- RELAYS FIRE:- 2 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
- RELAY FAULT:- 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
- GRAPHICAL LCD DISPLAY:- High definition, high contrast blue backlit 240×64 pixels
- COMMUNICATION CHANNELS:- 2 x configurable communications ports
- BMS OUTPUT:- ODYSSEY (Graphical software), TCP/IP WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
- SOFTWARE CONNECTION:- USB type B
- EVENT LOG:- 10,000 events
- OPERATING / STORAGE TEMPERATURE:- -10ºC to +50ºC
- HUMIDITY:- Max. 85% RH Non-Condensing
- INGRESS PROTECTION / MATERIAL:- IP30 / ABS
- DIMENSIONS:- Standard box: 273 (L) x 403 (H) x 106 (W) mm; Deep box: 273 (L) x 403 (H) x 142 (W) mm
- WEIGHT:- 1,6 Kg (no batteries)