Octo+ Large 1-12 Loop Fire Alarm Control Panel
Octo+ Large 1-12 Loop Fire Alarm Control Panel:
Key Features:
- Expandable from 1 to 12 loops
- Connection to the repeater panels via RS422, Fibre-Optic or TCP/IP Chameleon interfaces
- Maximum 125 devices per loop (500 devices per Node)
- Up to 95 VULCAN 2 (addressable) ultra low current base sounders (32 address limit) per loop
- 32 individually programmable sounder addresses per loop
- Full Self-Addressing Device support
- 6 Fire output relays (change-over) and 3 Fault relay (NC)
- 6 conventional alarm outputs (individually programmable)
- Fully monitored loops for high integrity OC / SC
- 384 fully programmable zones across all loops
- 512 fully programmable sounder groups, across all loops
- 512 I/O groups across all loops
- Built-in printer (optional)
- Available with ZEOS digital protocol
- Compatible with all ancillary modules
- Programming by integrated tactile keypad or Connected PC software (WIN & MAC compatible)
- Multiple language support (menu selectable)
- Optional Integrated 128 LED fire zone indications (available in blocks of 64 LEDs)
- Installer friendly Auto-learn facility
Technical Specification:
- POWER SUPPLY RATING:- 90V AC to 230V AC
- PRIMARY DC SUPPLY:- 28.5V DC @ 7.5 A (Max.) / 28.5V DC @ 10 A (Max.)
- SECONDARY SUPPLY:- 21.6V DC Min. – 27.2V DC Max. – Battery charger: 27.5V DC
- BATTERIES (INTERNAL):- 2 x 24V 12 AH (Max.)
- QUIESCENT CURRENT (NO DEVICES):- 75mA / 125mA/ 175mA (4, 8 and 12 Loops)
- AUX POWER OUTPUT:- 24V DC: 900 mA total (300 mA each NODE, having up to 3 switched outputs)
- MAXIMUM LOOP OUTPUT CURRENT:- 4 to 12 loops – Max. 165 mA per loop quiescent / Max. 900mA per loop peak
- LOOP TOPOLOGY:- Class A or B
- DETECTOR CABLE:- Firetuf 2 x 1,5 / max 2,000 m or 2 x 2,5mm / max 3,000m
- CONVENTIONAL SOUNDER CIRCUITS:- Up to 6 500 mA Max. current drive for both circuits – Fully monitored
- RELAYS FIRE:- Up to 6 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
- RELAY FAULT:- Up to 3 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive / 0.25A @ 240V AC resistive
- GRAPHICAL LCD DISPLAY:- 240×64 pixels blue backlit
- ZONE LEDS:- Maximum 128 Zone LED / blocks of 64 LED
- COMMUNICATION CHANNELS:- 3x configurable communication ports and per each NODE
- BMS OUTPUT:- ODYSSEY (Graphical software), TCP IP-WEB (remote web monitoring), MODBUS RTU, ESPA 4.4.4
- SOFTWARE CONNECTION:- USB type B
- EVENT LOG:- 10,000 messages
- OPERATING / STORAGE TEMPERATURE:- -10ºC to 50ºC
- HUMIDITY:- Max. 85% RH Non-Condensing
- PROTECTION:- IP30
- DIMENSIONS:- 610 (L) x 420 (H) x 179,1 (W) mm
- WEIGHT:- 6,1Kg (no batteries)
- COLOUR:- White (RAL 9003) or Red (RAL 3001)