OCTO + 1-4 Loop Fire Alarm Control Panel:

Key Features:

  • Expandable from 1 to 4 loops
  • Network compatibility with the G−One, GEKKO and NODE+ control panels
  • Connection to the repeater panels via RS422, Fibre−Optic or TCP/IP
  • 250 devices per loop (125 address limit)
  • Up to 95 VULCAN 2 (addressable) ultra low current base sounders (32 address limit)
  • 32 individually programmable sounder addresses
  • Full Self−Addressing Device support
  • 2 Fire output relays (change−over) and 1 Fault relay (NC )
  • 2 conventional alarm outputs (individually programmable)
  • Loops fully monitored for high integrity
  • 384 fully programmable zones
  • 512 fully programmable sounder groups
  • 512 I/O groups
  • Event log ( 10000 events)
  • Available with ZEOS digital protocol
  • Compatible with all ancillary modules
  • Backlit graphical LCD display of 240 x 64 pixels
  • Programming by integrated tactile keypad or Loader PC software
  • Multiple language support (menu selectable)
  • Integrated 16 LED fire zone indications
  • Installer friendly Auto−learn facility
  • Certified to EN54 parts 2 and 4

Technical Specifications:

  • POWER SUPPLY RATING:- 90V AC to 230V AC
  • PRIMARY DC SUPPLY:- 28.5V DC @ 2.4 A (Max.)
  • SECONDARY SUPPLY:- 21.6 Min. − 27.2V DC (Max.) − Battery charger: 27.5V DC
  • BATTERIES (INTERNAL):- 2 x 12V 12 AH (Max.)
  • QUIESCENT CURRENT (NO DEVICES):- 65 mA
  • AUX POWER OUTPUT:- 2 x 24V DC 300mA / up to 1 x 24V switched out
  • MAXIMUM LOOP OUTPUT CURRENT:- 1−4 loop − Max. 165 mA per loop quiescent / Max. 900mA per loop peak
  • LOOP TOPOLOGY:- Class A or B
  • DETECTOR CABLE:- Firetuf 2 x 1,5 / max 1,200 m or 2 x 2,5mm / max 2,000m
  • CONVENTIONAL SOUNDER CIRCUITS:- 2 x 250 mA Max current drive for each circuit − Fully monitored
  • RELAYS FIRE:- 2 x rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive
  • RELAY FAULT:- 1 rated 2A @ 30V DC resistive / 0.5A @ 120V AC resistive/ 0.25A @ 240V AC resistive
  • GRAPHICAL LCD DISPLAY:- 240×64 pixels blue backlit
  • COMMUNICATION CHANNELS:- 3x configurable communication ports
  • BMS OUTPUT:- ODYSSEY (Graphical software), TCP IP−WEB( remote web monitoring), MODBUS RTU, ESPA 4.4.4
  • SOFTWARE CONNECTION:- USB type B
  • EVENT LOG:- 10,000 messages
  • OPERATING/STORAGE TEMPERATURE:- −10ºC to 50ºC
  • HUMIDITY:- Max. 85% RH Non−Condensing
  • PROTECTION:- Surface Mount: IP30, Recessed Mount: IP65
  • DIMENSIONS:- 345 (L) x 375 (H) x 139 (W) mm
  • WEIGHT:- 7.5 Kg – 10.5 Kg (inc. 2 x 12 AH 12 V bat.)
  • COLOUR:- White (RAL 9003) and Red (RAL 3001)